K511 Single-phase Relay Tester
| ![]() |
|
|
![]() |
Catalogue

- All-in-one design with local microprocessor controlled and LCD display ;
- Max.1300VA power output & 200A/300V AC output;
- 300V Auxiliary DC with 0.5% accuracy;
- Meter input source testing of U,I,f,power and so on;
- Matches different types of clamping meter to meet the requirement of testing the high current, max. 1000A
- Max.1024 testing result report local memory saving,display&analyze;
- Test settings storing and recalling from the local memory;
- Testable without PC&PC upgrading
Main specifications:
|
Voltage generators
|
|
Setting
Range
|
1-phase AC (L-N)
|
1 x 0 ... 300 V
|
|
Power
|
1-phase AC (L-N)
|
200VA MAX. at 0…300V
|
|
Accuracy
|
0.4% reading + 0.1% range typical at 0-300V
|
|
Resolution
|
1mV
|
|
Current generators
|
|
Setting
Range
|
1-phase AC (L-N)
|
0-40A;0-200A
|
|
Power
|
1-phase AC (L-N)
|
1120 VA MAX.,at 0...40A ; 1200VA MAX., at 0-100A (12V);900VA MAX., at 0...200A(4.5V)
|
|
Accuracy
|
0.4% reading + 0.1% range typical at 0-200A
|
|
Resolution
|
1mA
|
|
Generators, general
|
|
Frequency
|
Range
|
5 ... 1000 Hz
|
|
Accuracy / drift
|
Error < 0.001Hz at 10 ... 50Hz, error < 0.01Hz at 50Hz... 1000Hz
|
|
Resolution
|
0.01Hz
|
|
Phase
|
Range
|
- 360° ... +360°
|
|
Accuracy / drift
|
Error < 0.2 °
|
|
Resolution
|
0.1°
|
|
Time
|
Range
|
0.001 ... 9999.999s
|
|
Accuracy / drift
|
Error<0.1ms
|
|
Resolution
|
1ms
|
|
DC generators
|
|
Voltage ranges
|
0 ... 300V/200W
|
|
Current ranges
|
0 ... 30A/840VA
|
|
Accuracy
|
|
|
Resolution
|
1mA; 1 mV
|
|
Ampere meter
|
|
Measurement method
|
TRMS (AC)
|
|
Range
|
0 – 5A (AC )
|
|
Accuracy
|
0.4% reading + 0.1% range
|
|
AC current clip-input test:
|
|
AC current input
|
5A/20A/100A/500A/1000A
|
|
Accuracy
|
0.5%
|
|
Voltage meter
|
|
Measurement method
|
TRMS(AC), Average value(DC)
|
|
Range
|
0-300 V
|
|
Accuracy
|
0.4%rd+0.1%rg
|
|
Power factor meter
|
|
Power factor(cos φ)Range
|
(-1.00)–1.00
|
|
Resolution
|
0.01
|
|
Accuracy
|
±0.04
|
|
Phase meter
|
|
Phase φ (°)
|
0- 359
|
|
Resolution
|
1
|
|
Accuracy
|
±1
|
|
Aux DC Supply
|
|
Range
|
0...300V/0.33A
|
|
Binary Inputs
|
|
Number
|
2 pairs
|
|
Compatible Voltage
|
30V ... 250VDC, or dry contact
|
|
Binary outputs
|
|
Number
|
1 Pair
|
|
Capacity
|
250V/3A(AC,DC)
|
|
Power supply
|
|
Nominal input voltage
|
110/220V AC ±10%
|
|
Power
|
1000VA
|
|
Nominal frequency
|
50/60±5Hz
|
|
Environmental conditions
|
|
Operation temperature
|
-5°C ...55 °C
|
|
Storage temperature
|
-20°C ... 75 °C
|
|
Humidity range
|
5 ... 95 %, non-condensing
|
|
Weight
|
24KG
|
|
Dimensions
|
365 (W) ×465(D)×160 (H) mm
|
|
PC Interface
|
RJ45
|
K511 Series Protection Relay Test Set:
|
Model
|
Channels
|
AC Outputs
|
|
K511
|
3 output channels
|
1*40A/1*200A/1*300V
|
Major functions:
|
Items
|
IEEE(R) No.
|
|
Overcurrent relays
|
50/76
|
|
Inverse time overcurrent relays
|
51
|
|
Undercurrent relays
|
37
|
|
Directional overcurrent relays
|
67
|
|
Overvoltage relays
|
59
|
|
Undervoltage relays
|
27
|
|
Directional voltage relays
|
91
|
|
Time-delay relays
|
|
|
|
|