K50 Series Protection Relay Test Set
| ![]() |
|
|
![]() |
Catalogue

- Use reliability is ensured by its AC measurement and waveform recording, and automatic detection is performed after the relay test set start running, which are independently developed by Kingsin Electric Automation Co.Ltd.
- All-in-one designed Relay Test Set: built-in industrial computer, embedded style Windows CE system, with stable and reliable performance; mouse and keyboard built in panel or external connection available; LCD display; Windows operation interface;
- Wide Application from old Electromechanic relay to Modern digital protection relay.Suitable working for many world famous brand protection relays.Such as ABB, ALSTOM, SCHNEIDER, SIEMENS, GE, SEL etc;
- Simultaneous output of 7 voltage and 6 current; amplitude, phase and frequency adjustable independently;
- Adjusting output precision by software;
- Self-protection functions, such as voltage short circuit protection, current open circuit, and external source unexpected input, not well grounding etc;
- Adopt EMC box and have CE approved;
- Providing 23 pcs function modules of relay protection testing;
- Interfaces: RJ45 (PC communications), USB (report upload & software upgrade), GPS interface (multi-tester synchronizing working), VGA (projector for training demonstration), PS/2 (keyboard and mouse);
- Communications protocol for users, and user defines test solutions according to demands;
- Upright or horizontal design for box, and independent operation even without the testing bench.
Technical Data of K5063i
|
Voltage generators
|
|
Setting
Range
|
4-phase AC (L-N)
|
4 x 0 ... 130 V
|
|
1-phase AC (L-L)
|
1 x 0 ... 260 V
|
|
Power
|
4-phase AC (L-N)
|
4 x70VA, at 0 ... 130 V
|
|
1-phase AC (L-L)
|
1 x 120VA, at 0 ... 260 V
|
|
Accuracy
|
<0.07% reading + 0.03% range guaranteed at 0-130V
<0.04% reading + 0.01% range typical at 0-130V
|
|
Resolution
|
1mV
|
|
Current generators
|
|
Setting
Range
|
3-phase AC (L-N)
|
3 x 0 ... 30 A
|
|
1-phase AC (3L-N)
|
1 x 0 ... 90 A
|
|
Power
|
3-phase AC (L-N)
|
1x 600VA, at 0 ... 30A
|
|
1-phase AC (3L-N)
|
1 x 1000 VA, at 0 ...90A
|
|
Accuracy
|
<0.14% reading + 0.06% range guaranteed at 0-30A
<0.05% reading + 0.02% range typical at 0-30A
|
|
Resolution
|
1mA
|
|
Generators, general
|
|
Frequency
|
Range
|
0 ... 1000 Hz
|
|
Accuracy / drift
|
Error < 0.001Hz at 10 ... 450Hz, error < 0.01Hz at 50Hz... 450Hz
|
|
Resolution
|
0.001Hz
|
|
Phase
|
Range
|
- 360° ... +360°
|
|
Accuracy / drift
|
Error < 0.2 °
|
|
Resolution
|
0.01°
|
|
Time
|
Range
|
0 ... 999.999s
|
|
Accuracy / drift
|
Error<0.1ms
|
|
DC generators
|
|
Voltage ranges
|
0 ... 300V/150VA
|
|
Current ranges
|
0 ... 20A/300W
|
|
Accuracy
|
Error< 0.2%
|
|
Resolution
|
1mA; 1 mV
|
|
Aux DC Supply
|
|
Range
|
0...300V/0.4A
|
|
Binary inputs
|
|
Number
|
8 pairs
|
|
Compatible Voltage
|
10V ... 250V
|
|
Binary outputs
|
|
Number
|
4 Pairs
|
|
Capacity
|
250V/2A
|
|
Synchronization
|
|
Synchronization mode
|
GPS
|
|
Harmonic
|
|
Harmonic overlap times
|
2 ... 20 times
|
|
Power supply
|
|
Nominal input voltage
|
85V...264VAC, 1-phase
|
|
Power
|
1000VA
|
|
Nominal frequency
|
50±10% Hz
|
|
Environmental conditions
|
|
Operation temperature
|
-5°C ...55 °C
|
|
Storage temperature
|
-20°C ... 75 °C
|
|
Humidity range
|
5% ... 90 %, non-condensing
|
|
Weight
|
17.5 KG
|
|
Dimensions
|
420(D)×140 (W)×360 (H) mm
|
|
Interface
|
RJ45
|
Major functions:
|
Items
|
IEEE(R) No.
|
|
Synchronization relay
|
|
|
Fault transplay
|
|
|
GPS Synchronization
|
|
|
Overcurrent relays
|
50/76
|
|
Inverse time overcurrent relays
|
51
|
|
Undercurrent relays
|
37
|
|
Ground fault relays
|
50
|
|
Directional overcurrent relays
|
67
|
|
Directional ground fault relays
|
67N
|
|
Overvoltage relays
|
59
|
|
Undervoltage relays
|
27
|
|
Directional voltage relays
|
91
|
|
Directional power relays
|
32
|
|
Power factor relays
|
55
|
|
Differential protection (differential circuits)
|
87
|
|
Distance protection equipment (phase by phase)
|
21
|
|
Negative sequence overcurrent relays
|
46N
|
|
Motor overload protection
|
51/86
|
|
Automatic reclosing devices
|
79
|
|
Tripping relays
|
94
|
|
Voltage regulating relays
|
|
|
Overimpedance relays, Z>
|
|
|
Underimpedance relays, Z
|
|
|