Catalogue

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;
Technical Data of K3063Li
|
Voltage generators
|
|
Setting
Range
|
4-phase AC (L-N)
|
4 x 0 ... 300 V
|
|
2-phase AC (L-L)
|
2 x 0 ... 600 V
|
|
Power
|
4-phase AC (L-N)
|
4 x 110VA, at 0 ... 300 V
|
|
2-phase AC (L-L)
|
2 x 220VA, at 0 ... 600 V
|
|
Accuracy
|
<0.07% reading + 0.03% range guaranteed
at 0 ... 300 V
<0.02% reading + 0.01% range typical
at 0-300V
|
|
Resolution
|
1mV
|
|
Current generators
|
|
Setting
Range
|
6-phase AC (L-N)
|
6 x 0 ... 30 A
|
|
3-phase AC (L-N)
|
3 x 0 ... 60 A (Group A II B)
|
|
1-phase AC (3L-N)
|
1 x 0 ... 180 A
|
|
Power
|
6-phase AC (L-N)
|
6x 450VA ,at 0 ... 30A
|
|
3-phase AC (L-N)
|
3x 900VA, at 0 ... 60A (Group A II B)
|
|
1-phase AC (3L-N)
|
1 x 1500 VA, at 0 ... 180A (Max.)
|
|
Accuracy
|
<0.07% reading + 0.06% range guaranteed at 0-30A
<0.02% reading + 0.02% range typical at 0-30A
|
|
Resolution
|
1mA
|
|
Generators, general
|
|
Frequency
|
Range
|
0 ... 1000 Hz
|
|
Accuracy / drift
|
Error < 0.001Hz at 0 ... 450Hz, error < 0.01Hz at 450…1000 Hz
|
|
Resolution
|
0.001Hz
|
|
Phase
|
Range
|
- 360° ... +360°
|
|
Accuracy / drift
|
Error < 0.2 °
|
|
Resolution
|
0.1°
|
|
Timer
|
Range
|
Infinite
|
|
Accuracy / drift
|
Error<0.1ms
|
|
DC generators
|
|
Voltage ranges
|
0 ... 300V/180W
|
|
Current ranges
|
0 ... 20A/300W
|
|
Accuracy
|
<0.07% reading + 0.03% range guaranteed at 0-300V
<0.04% reading + 0.02% range typical at 0-300V
|
|
<0.14% reading + 0.06% range guaranteed at 0-20A
<0.05% reading + 0.02% range typical at 0-20A
|
|
Resolution
|
1mA; 1 mV
|
|
Aux DC Supply
|
|
Range
|
0...300V/0.6A
|
|
Binary inputs
|
|
Number
|
8 pairs
|
|
Compatible Voltage
|
10V ... 250V/2A
|
|
Binary outputs
|
|
Number
|
4 Pairs
|
|
Capacity
|
250V/2A
|
|
Synchronization
|
|
Synchronization mode
|
GPS
|
|
Harmonic
|
|
Harmonic overlap times
|
2 ... 20 times
|
|
Power supply
|
|
Nominal input voltage
|
85V…264V ac
|
|
Power
|
1000VA
|
|
Nominal frequency
|
47Hz….65Hz
|
|
Environmental conditions
|
|
Operation temperature
|
-5°C ... 55 °C
|
|
Storage temperature
|
-20°C ... 75 °C
|
|
Humidity range
|
5% ... 90 %, non-condensing
|
|
Weight
|
17.8 KG
|
|
Dimensions
|
480(D)×140 (W)×360 (H) mm
|
|
PC connection
|
RJ45
|
K30 Series Protection Relay Test Set:
|
Model
|
Channels
|
AC Outputs
|
|
K3063i / K3063Li
|
10 output channels
|
6*30A/3*40A/4*300V
|
|
K3030i / K3030Li
|
7 output channels
|
3*30A/4*300V
|
|
K3066
|
13 output channels
|
6*20A/3*40A/7*130V
|
|
K3063
|
10 output channels
|
6*20A/3*40A/4*130V
|
|
K3040
|
7 output channels
|
3*40A/4*130V
|
|
K3030
|
7 output channels
|
3*30A/4*130V
|
Major functions:
|
Items
|
IEEE(R) No.
|
|
Synchronization relay
|
|
|
Fault transplay
|
|
|
GPS Synchronization
|
|
|
Overcurrent relays
|
50/76
|
|
Inverse time overcurrent relays
|
51
|
|
Undercurrent relays
|
37
|
|
Ground fault relays
|
50
|
|
Directional overcurrent relays
|
67
|
|
Directional ground fault relays
|
67N
|
|
Overvoltage relays
|
59
|
|
Undervoltage relays
|
27
|
|
Directional voltage relays
|
91
|
|
Directional power relays
|
32
|
|
Power factor relays
|
55
|
|
Differential protection (differential circuits)
|
87
|
|
Distance protection equipment (phase by phase)
|
21
|
|
Negative sequence overcurrent relays
|
46N
|
|
Motor overload protection
|
51/86
|
|
Automatic reclosing devices
|
79
|
|
Tripping relays
|
94
|
|
Voltage regulating relays
|
|
|
Overimpedance relays, Z>
|
|
|
Underimpedance relays, Z
|
|
|
Time-delay relays
|
|
|