KS706 Portable Reference Standard
| ![]() |
|
|
![]() |
Catalogue

- Auto switching available to choose from voltage measuring range and current measuring range, and all the energy constants of the measuring range can remains;
- Available to display the measurement data and waveform of three voltage and three current; and able to analyse harmonic within 21 orders.
- Able to identify these frequently faced wrong connections as 3-phase & 3wire (48 types), and 3-phase & 4 wire(96 types), and display hexagon diagram of optional connection;
- Error correction function is provided to help user do error calibration, parameter measurement data will make correction;
- Built-in industrial computer is adopted to control the device plus with the ports convenient for function extension, user-friendly interface style and rich content ;
- Colorful LCD: 6.4 inch, resolution 640X480;
- Auto/Manual calibration for energy meter based on single phase, 3-phase & 3wire, 3-phase & 4-wire active, 3-phase & 4-wire reactive inductive and 3-phase & 4-wire activeelectronic (able to receive the pulse of electronic energy meter); utilizing antitheses method to calibrate voltage, current, power, power factor, phase and frequency for electrotechnical instruments and transducers;
- Able to create a new file or open the existed on-site library file, and delete or inquire the record of library files;
- Data tranmission by U disk; Convenient software updating through LAN or U disk;
Main specifications:
|
AC Voltage input test
|
|
Auto-handover range:
|
30V~456V
|
|
Voltage range:
|
100V/220V/400V
|
|
Accuracy:
|
0.05%
|
|
AC current direct input test
|
|
Auto-handover range:
|
0.05A~10A
|
|
Current range:
|
0.2A/0.5A/1A/2A/5A/10A
|
|
Accuracy:
|
0.05%
|
|
AC current clip-input test
|
|
AC current input
|
5A
|
|
Accuracy
|
0.2%
|
|
AC current clip-input test:
|
|
AC current input
|
20A/100A/500A/1000A
|
|
Accuracy
|
0.5%
|
|
Power & Electric Energy Test
|
|
AC current clip-input test:
|
|
Active Power & Electric Energy test accuracy:
|
0.05%
|
|
Reactive Power Accuracy
|
0.2%
|
|
AC current 5A clip-input test:
|
|
Active Power & Electric Energy test accuracy:
|
0.2%
|
|
Reactive Power Accuracy
|
0.5%
|
|
Power factor test scope :
|
-1~+1
|
|
Accuracy:
|
±0.0005
|
|
Phase test scope :
|
-180~+180°
|
|
Accuracy:
|
±0.05°
|
|
Frequency test scope :
|
45 Hz ~ 65 Hz
|
|
Accuracy:
|
±0.01 Hz
|
|
Current & Voltage humorous test:
|
2-21orders humorous
|
|
Warming-up:
|
≤ 10 minutes
|
|
Standard Electric Energy pulse setting:
|
|
Direct-input:
|
Default 36000000p/kWh for full range.
|
|
|
36000000p/kWh for 100V;
|
|
|
18000000p/kWh for 200V;
|
|
|
9000000p/kWh for 400V;
|
|
Current Clamp input:
|
Default 36000000 / (clip range /5) p/kWh
|
|
|
36000000 / (clip range /5) p/kWh for 100V;
|
|
|
18000000 / (clip range /5) p/kWh for 200V;
|
|
|
9000000 / (clip range /5) p/kWh for 400V;
|
|
Output Electric Energy Constant:
|
100~360000000
|
|
Working environment
|
|
Working temperature :
|
0 ~ 40°C
|
|
Humidity
|
≤85%
|
|
Working power supply :
|
AC 85V-260V
|
|
Consumption:
|
≤15VA
|
|
|
|