The Property of Phase Distance

Protection Relay test Set: K10\K20\K30 Series
Device model:
GE L90 Line Differential Relay

Bill of fixed value:

Parament
Phase Distance Z1
Function
Enable
Direction
Forward
Shape
Quad 
Xfmr Vol Connection
None
Xfmr Curr Connection 
None  
Reach
1.40ohm
RCA
85 deg 
Comp Limit
90 deg
DIR RCA
60 deg
DIR Comp Limit
70 deg
Quad Right Blinder
1.20ohm
Quad Right Blinder RCA
70 deg
Quad Left Blinder
0.80ohm
Quad Left Blinder RCA
80 deg
 


Phase Distance Graph (GE Software)
 
Testing Connection:
A. Connect the output terminals of three-phase voltage and current IA of the relay test set with the corresponding input terminals of the protection device by test wire.
B. The triggering contact of the protection device is connected with Binary Input terminal A of the relay test set.
C.Open Advanced Distance I moudle,setting test parament
 
Parameter Setup



Basic parament



Time and fault type

After the setup is finished, click ‘Run’ button on the right upper corner and begin the test;

Result graph