中文 English Русский Français
Technical support
Customer support
Solution
FAQ
 
Home >> Support >> Demostration_info

The Property of Grounding Distance

Protection Relay test Set: K10\K20\K30 Series
Device model:GE L90 Line Differential Relay
 

Bill of fixed value:

Parament
Grounding Distance Z1
Function
Enable
Direction
Forward
Shape
Mho 
Z0/Z1 Mag
1.00
Z0/Z1 Ang
0 deg  
ZOM Z1 Mag
0.00
ZOM Z1 Mag
0 deg 
Reach
1.00 ohm
RCA
75 deg
Rev Reach
1.00 ohm
Rev Reach RCA
75 deg
POL Current
Zero-Seq
DIR RCA
60 deg
DIR Comp Limit
70 deg
Quad Right Blinder
10 ohm
Quad Right Blinder RCA
85 deg
Quad Left Blinder
10 ohm
Quad Left Blinder RCA
85 deg

 
Grounding distance graph (GE Software)


Testing Connection:
A. Connect the output terminals of three-phase voltage and current IA of the relay test set with the corresponding input terminals of the protection device by test wire.
B. The triggering contact of the protection device is connected with Binary Input terminal A of the relay test set.
C.Open Advanced Distance I moudle,setting test parament
 
 

Parament Setup


 
   
Basic parament



Time and fault type

After the setup is finished, click ‘Run’ button on the right upper corner and begin the test;

 Result graph

 

 

 

Contact us
 Copyright 2009 KINGSINE. 粤ICP备05013578号 All Right Reserved