Curve of Differential Protection Ratio (AREVA P632)


Device model:AREVA P632 Differential Relay

 
Protection Relay test Set: K10\K20\K30 Series




 Testing Connection:
A. Connect the output terminals of current IA IBIC of the relay test set with the corresponding input terminals of the protection device by test wire.
B. The triggering contact of the protection device is connected with Binary Input terminal A of the relay test set.
C.Open Differential moudle,setting test parament
 

Parament Setup







After the setup is finished, click ‘Run’ button on the right upper corner and begin the test; 


Report

 

Bill of fixed value:

Parament

VALUE

Inom C.T.prim. end.a :

600A

Inom C.T.prim. end.b :

1500A

Inom device. end.a :

1.0A

Inom device. end.b :

1.0A

DIFF:Reference power sref:

50.0 MVA

Vnom prim. end. a :

35.0 KV

Vnom prim. end. b :

10.5 KV

DIFF:Vec.gr.ends a-b PS1:

11

Idiff>

2.5 Iref

Idiff>>

8.6 Iref

Idiff>>>

9.6 Iref

m1:

0.3

m2:

0.7

IR,m1:

0.5 Iref

IR,m2:

4.0 Iref

Op.mode.rush rst.:Not phase

selective

Rush I (2 f0 ) / I (f0 ):20%

20%

0- seq. filt .a en.     :

No

0-seq. filt .b en.     :

No

Overflux. bl. en.    :

No