Catalogue

1. Adopts 6.4 large LCD screen, and provided with VGA video interface, making it available to connect to projector for training;
2. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
3. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A(Poleless and adjustable);
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Function of transducer and energy meter testing (optional function);
6. Adopt Smart and stable Window CE embedded system. Windows has the advantage of small application program with fast speed, which overcomes the problem of bad stability, easy-damage hardware, and virus of Windows 98/2000/XP;
7. Use high-speed CF card as the storage, more stable, anti-shock compared with ordinary hardware, so works more reliable.
Main specifications:
|
Voltage generators
|
|
Setting
Range
|
7-phase AC (L-N)
|
7 x 0 ... 130 V
|
|
1-phase AC (L-L)
|
1 x 0 ... 260 V
|
|
Power
|
7-phase AC (L-N)
|
7 x 70VA, at 0 ... 130 V
|
|
1-phase AC (L-L)
|
1 x 140VA, at 0 ... 260 V
|
|
Accuracy
|
<0.07% reading + 0.03% range guaranteed at 0-130V
<0.04% reading + 0.01% range typical at 0-130V
|
|
Resolution
|
1mV
|
|
Current generators
|
|
Setting
Range
|
6-phase AC (L-N)
|
6 x 0 ... 20 A
|
|
3-phase AC (L-N)
|
3 x 0 ... 40 A (Group A II B)
|
|
1-phase AC (3L-N)
|
1 x 0 ... 120 A
|
|
Power
|
6-phase AC (L-N)
|
6 x 150 VA ,at 0 ... 20A Max 250VA,with the other current channels unload
|
|
3-phase AC (L-N)
|
3 x 300VA, at 0 ... 40A (Group A II B) Max 450VA, with the other current channels unload
|
|
1-phase AC (3L-N)
|
1 x 900 VA
|
|
Accuracy
|
<0.14% reading + 0.06% range guaranteed at 0-40A
<0.05% reading + 0.02% range typical at 0-40A
|
|
Resolution
|
1mA
|
|
Generators, general
|
|
Frequency
|
Range
|
0 ... 1000 Hz
|
|
Accuracy / drift
|
Error < 0.001Hz at 0 ... 50Hz, error < 0.0002Hz at 50Hz
|
|
Resolution
|
0.01Hz
|
|
Phase
|
Range
|
- 360° ... +360°
|
|
Accuracy / drift
|
Error < 0.2 °
|
|
Resolution
|
0.1°
|
|
Time
|
Range
|
0 ... 999.999s
|
|
Accuracy / drift
|
Error<0.1ms
|
|
Resolution
|
10μs
|
|
DC generators
|
|
Voltage ranges
|
0 ... 300V/150VA
|
|
Current ranges
|
0 ... 20A/300W
|
|
Accuracy
|
Error<0.2%
|
|
Resolution
|
1mA; 1 mV
|
|
Harmonic
|
|
|
Harmonic superpose times
|
2 ... 20
|
|
Aux DC Supply
|
|
Range
|
0...250V/0.6A
|
|
Binary Inputs
|
|
Number
|
8 pairs
|
|
Compatible Voltage
|
10V ... 250V
|
|
Binary outputs
|
|
Number
|
4 Pairs
|
|
Capacity
|
250V/2A
|
|
Synchronization
|
|
Synchronization mode
|
GPS
|
|
Power supply
|
|
Nominal input voltage
|
220V±10% VAC, 1-phase
|
|
Power
|
1000VA
|
|
Nominal frequency
|
50±10% Hz
|
|
Environmental conditions
|
|
Operation temperature
|
0°C ...60 °C
|
|
Storage temperature
|
-20°C ... 70 °C
|
|
Humidity range
|
5 ... 90 %, non-condensing
|
|
Weight
|
24KG
|
|
Dimensions
|
420(D)×140 (W)×360 (H) mm
|
|
Interface
|
RJ45 ,USB,RS232,PS/2,VGA
|
|
PC Connection
|
RJ45
|
K10 Series Protection Relay Test Set:
|
Model
|
Channels
|
AC Outputs
|
|
K1063i
|
10 output channels
|
6*30A/3*60A/4*300V
|
|
K1066i
|
13 output channels
|
6*30A/3*60A/7*300V
|
|
K1066
|
13 output channels
|
6*20A/3*40A/7*130V
|
|
K1066+
|
13 output channels,
|
6*30A/3*60A/7*130V
|
|
K1063
|
10 output channels
|
6*20A/3*40A/4*130V
|
|
K1036
|
10 output channels
|
3*40A/7*130V
|
|
K1040
|
7 output channels
|
3*40A/4*130V
|
|
K1030
|
7 output channels
|
3*30A/4*130V
|
Major functions:
|
Items
|
IEEE(R) No.
|
|
Synchronization relay
|
|
|
Fault transplay
|
|
|
GPS Synchronization
|
|
|
Overcurrent relays
|
50/76
|
|
Inverse time overcurrent relays
|
51
|
|
Undercurrent relays
|
37
|
|
Ground fault relays
|
50
|
|
Directional overcurrent relays
|
67
|
|
Directional ground fault relays
|
67N
|
|
Overvoltage relays
|
59
|
|
Undervoltage relays
|
27
|
|
Directional voltage relays
|
91
|
|
Directional power relays
|
32
|
|
Power factor relays
|
55
|
|
Differential protection (differential circuits)
|
87
|
|
Distance protection equipment (phase by phase)
|
21
|
|
Negative sequence overcurrent relays
|
46N
|
|
Motor overload protection
|
51/86
|
|
Automatic reclosing devices
|
79
|
|
Tripping relays
|
94
|
|
Voltage regulating relays
|
|
|
Overimpedance relays, Z>
|
|
|
Underimpedance relays, Z
|
|
|
Time-delay relays
|
|
|
|
|
|