Kingsine Electric Automation Co., Ltd.

     Specialize in Electric Power Testing

 

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsRelay Test Set

Universal Relay Test Set Complied IEC61850

Certification
Good quality Relay Test Set for sales
Good quality Relay Test Set for sales
KINGSINE is a reliable company with good quality products, reasonable price and perfect service.

—— Mike Moeller

To do business with KINGSINE is a satisfying experience,they provide Prompt reply and best Technical support.

—— Joseph

I'm Online Chat Now

Universal Relay Test Set Complied IEC61850

China Universal Relay Test Set Complied IEC61850 supplier

Large Image :  Universal Relay Test Set Complied IEC61850

Product Details:

Place of Origin: China
Brand Name: Kingsine
Certification: ISO9001,CE
Model Number: K3163i

Payment & Shipping Terms:

Minimum Order Quantity: 1 set
Delivery Time: 15 working days
Payment Terms: T/T in advance ,L/C
Supply Ability: 50 sets/ month
Detailed Product Description
Analog Signal Channels: 6X30A,4X300V

Product Feature

Suitable testing for all kinds of Electromagnetics relays, Microcomputer relays; complete compling IEC61850/IEC60044-7/8 protocols, Facility for Merge Unit, and Numerical IED relays test.

 

100Mbit fiber ports, 10/100/1000Mbit Ethernet transfer multi-groups SMV and GOOSE, each SMV ability configure up to 64 sampling channels.

 

Able for subscriptions & simulations GOOSE, SMV messages signal.

 

Facility import/export/download/save Substation Configuration Language files (SCD/ICD/CID/NPI format files).

 

Simulate abnormal network fault conditions (Loss frame, mis-ordering, quality abnormal, message resend, data unusual, synchronism etc).

 

13 low-level signal outputs for low-level protection relay testing.

 

Facility for energy meter and transducer calibrate.

 

AC/DC measurement, 0~600V, 0~5A.

 

Facility for pulse count.

 

Technical Parameters

Analog Generators

Current

AC 6X30A @ 450VA

AC 3X60A @ 850VA

AC 1X100A @ 1000VA

DC 6X20A @ 300W

Current Accuracy

<0.05%rd+0.02%rg,typ

<0.15%rd+0.05%rg,Guar

Voltage

AC 4X300V L-N @ 120VA Max

AC 2X600V L-L @ 240VA Max

DC 3X300V @ 120W

Voltage Accuracy

<0.07%rd+0.03%rg.guar. @ 0~300V

<0.03%rd+0.01%rg.typ. @ 0~300v

Distortion

<0.1%guar.(<0.05%typ)

Auxiliary DC:

0~300V @ 120W Max

0.5%rg guar

13 Low-level outputs

Quantity

13channels,Aviation connector

Output Power

AC 0~8Vrms,DC 0~10v

Current

Rating 2Ma, 10mA transient max.

Power

≥0.5VA

Accuracy

<0.2%(0.01~0.8Vrms)

<0.1%(0.8~8Vrms)

Resolution

250Uv

Distortion (THD %)

<0.1%guar.(<0.05%typ)

IEC61850 Fiber & GOOSE Ethernet Ports

Mode 1

1X100Base-FX Full Duplex,LC type

 Mode 2

1XEthernet,10/100/1000Mbit,RJ45 type

Resolution

0.001Hz

Fiber Type

62.5/125um(Multiple optical fiber, Orange Red)

Wavelength

1310nm

Transmit distance

>1km

Indicator

SPD Green(light):valid connection

Link/Act Yellow(blinking):Data exchanging

Note

All hardware ready for activate

Frequency & Phase angle

Frequency Range

DC~1KHz,3KHz transient

Frequency Accuracy

±1ppm

Frequency Resolution

0.001Hz

Phase Angle

-360~+360°

Phase Accuracy

<0.05°typ,<0.1°Guar,50/60Hz

Phase Resolution

0.001°

Binary Input

Quantity

8pairs

Type

Wet/dry, pulse count, measurement

Threshold

0~600Vdc or potential free,Programable

Sample Rate

10KHz

Time Resolution

100us

Debounce Time

0~25ms(Software Controlled)

Time Range

Infinite

Time Errors

±1ms @ 0.001~1s

±0.1% @ >1s

Galvanic Isolation

4 isolated with each 2pairs

Input Impedance

600KΩ

Binary Outputs(Relay Type)

Quantity

4 pairs

Type

Potential free relay contacts, software controlled

Break capacity AC

Vmax:400Vac/Imax:8A/Pmax:2500VA

Break capacity DC

Vmax:300Vdc/Imax:5A/Pmax:150W

Binary outputs(Hi-speed Semiconductor)

Quantity

4 pairs semiconductor

Type

Open-collector, Aviation connector

Break capacity DC

Vmax:350Vdc

Ac(p-p)/Imax:0.5A/Pmax:150W

Response time

100us

AC/DC Measurement

Voltage Range

0~600Vrms(Rg:0.1V,0.6V,6V,60V,600V)

Voltage Accuracy

<0.1%rg

Current Range

0~5Arms(clamp input)

Current Accuracy

<0.1%rg

Frequency Range

45~65Hz,Accuracy <0.01Hz

Phase Accuracy

0~360°,<0.2°typ

Harmonic

2~20times,<0.5%rg

Transducer Calibration

DC Current

Range

DC: 0~±1Ma;1~±20Ma;Auto range

Max.input

600mA

Input Impedance

15Ω

Accuracy

<0.02%rg typ <0.05%rg Guar

DC Voltage

Range

DC 0~±10V

Max.input

±11V

Input Impedance

1MΩ

Accuracy

<0.02%rg typ <0.05%rg Guar

Energy Meter Calibration

Sensor Usage

Mechanical meters/Electronic meters

Sensor Output

High level:≥4.5V Low level:≤0.2V

Accuracy

<0.05% RG

Pulse Input

1 pulse input ports

Pulse Range

500KHz pulse input max

Pulse Output

1 transistor outputs

Size & Weight

PC Connection

1X10/100/1000M Base-Tx RJ45 Ethernet

Synchronizer port

IRIG-B,GPS SMA Antenna,IEEE1588

Others

RS-232

Aviation connector for pulse I/O and Binary output

Size

460X150X380mm

Weight

<19kg

Power Supply & Environment

Nominal input voltage

220Vac

Permissible input

100~264Vac

Nominal frequency

50/60Hz

Permissible frequency

45~65Hz

Power Consumption

1500VA max

Temperature(Operating)

0~ 55℃

Temperature(Storage)

-20~70℃

Humidity

5%-95%RH,non-condensing

Contact Details