Home ProductsProtection Relay Testing

KF86P Electronic Protection Relay Test Light Weight 6x35A

Certification
China Kingsine Electric Automation Co., Ltd. certification
China Kingsine Electric Automation Co., Ltd. certification
Customer Reviews
KINGSINE is a reliable company with good quality products, reasonable price and perfect service.

—— Mike Moeller

To do business with KINGSINE is a satisfying experience,they provide Prompt reply and best Technical support.

—— Joseph

I'm Online Chat Now

KF86P Electronic Protection Relay Test Light Weight 6x35A

KF86P Electronic Protection Relay Test Light Weight  6x35A
KF86P Electronic Protection Relay Test Light Weight  6x35A

Large Image :  KF86P Electronic Protection Relay Test Light Weight 6x35A

Product Details:
Place of Origin: China
Brand Name: KINGSINE
Certification: CE/ISO9001
Model Number: KF86P
Payment & Shipping Terms:
Minimum Order Quantity: 1set
Price: negotiation
Delivery Time: 15 working days
Payment Terms: L/C, T/T
Supply Ability: 100sets per month
Detailed Product Description
Power: Electronic Usage: Protection Relay Test Set
Weight: 16kg Protect Feature: Sealed
Time Measurement Range: 1ms ~ 9999s Frequency Range: 0--1000Hz
High Light:

Electronic Protection Relay Test

,

KF86P Protection Relay Test

,

KF86P Protection relay tester

Light weight: 10kg, very small size (390mm*256mm*140mm) easy carry on flight journey.
6x35A, 6x310V analog output channels.
Compact 6-phase relay test set with high accuracy & full solution (complying IEC61850 sampled value and GOOSE), fully meet all the requirements for detection and debugging of IEC61850 IEDs, Merge Units, station control systems and traditional protection relays.

 

Description:

 

Features:

With analog (6x310V voltage, 6x35A current) and IEC61850 SMV messages simultaneously output;
Built-in dual-core CPU industrial computer, built-in large-capacity SSD solid drive; operating system Embedded Windows 7; 9.7-inch true color LCD screen, 1024×768 resolution, touch screen operation. Can work offline or online;
Provide 8 pairs of LC optical ports, can transmission and receive 36 channels of IEC61850-9-1, IEC61850-9-2 frame format sample values; with optical power test function;
Provide 6 ST output optical ports and 2 ST receive optical ports, which can output 6 sets of sampled value messages conforming to IEC60044-7/8 (FT3) format; can receive 2 sets of FT3 format of IEC60044-7/8 specification Sampled value message;
Can subscribe/publish GOOSE information or output, receive switching, and realize closed-loop testing of protection;
Simulate 12-channel low level output to test the protection of low level input;
Start up to simulate the IED to actively release GOOSE, sampled value signals, to eliminate the reset process of the device under test caused by link interruption after the test is stopped;
The optical port output is sampled or GOOSE can be freely defined; multiple different GOOSE control block information can be subscribed/published;
Sample value channel function, the number of channels can be set freely, up to 36 channels can be configured;
Automatically import SCL (SCD, ICD, CID, NPI) files to realize automatic configuration of sampled values and GOOSE information, and save sample values and GOOSE configuration information as a configuration file for testing;
It can automatically detect optical digital signals from MU, protection device and intelligent operation box, and realize automatic configuration function of sampling value and GOOSE information;
Can simulate abnormal conditions(loss, misorder, quality abnormality, message re-transmission, data anomaly, out of step, etc.);
The channel quality of the output SV message can be set, and the simulation unit can be simulated and debug, set to invalid, set to run state, and can simulate double AD inconsistency and other tests;
Support the graphical display of SCD files, the instrument can graphically display the IED device interconnection relationship and virtual terminal connection;
With the IRIG-B code transmission function, when the external GPS is used, it can be used as a timing device.


Graphical software interface:

KF86P Electronic Protection Relay Test Light Weight  6x35A 0

KF86P Electronic Protection Relay Test Light Weight  6x35A 1

 

KF86P Electronic Protection Relay Test Light Weight  6x35A 2

 

Specifications:

 

AC current source
Amplitude & Power 6×35A @ >425VA max each;
3×70A @ >670VA max each;
Accuracy ±1mA @ <0.5A
<0.015%Rd+0.005Rg Typ. @ 0.5A~35A
<0.04%Rd+0.01Rg Guar. @ 0.5A~35A
Range Range I: 3A
Range II: 35A
Automatic Range
DC Offset <3mA Typ./ <10mA Guar
Resolution 1mA
Distortion <0.025%Typ. / <0.07% Guar.
Ascends/Descent response <100us
DC Current source
Amplitude & Power 3×20A @ 400W max
Accuracy ±5mA @ <1A
±0.2% @ ≥1A
Ascends/Descent response <100us
AC voltage source
Amplitude & Power 6×310V @ 105VA max each,3×620V @ 210VA max each
Accuracy ±2mV @ <2V
<0.015%Rd+0.005Rg Typ. @ 2~310V
<0.04%Rd+0.01Rg Guar. @ 2~310V
Range Range I: 31V
Range II: 310V
Automatic Range
DC Offset <10mV Typ./ <60mV Guar
Resolution 1mV
Distortion <0.015%Typ. / <0.05% Guar.
Ascends/Descent response <100us
DC Voltage source
Amplitude & Power 4×350V @ 100W max
2×700V @ 150W max
Accuracy ±10mV @ <5V
±0.2% @ ≥5V
Ascends/Descent response <100us
Auxiliary DC Supply
Range 10~300Vdc
Power >70W max
Accuracy 1%Rg Guar.
Frequency & Phase Angle
Frequency Range DC ~ 1000Hz, 3000Hz transient
Frequency Accuracy ±0.5ppm
Frequency Resolution 0.001Hz
Phase Range -360°~360°
Phase Accuracy <0.05° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution 0.001°
Binary input
Electrical isolation 8 pairs of electrical isolated each
Input impedance 5 kΩ…13kΩ(Empty contact)
Input feature 0 V~300Vdc Or dry contact
(Binary input turn over potential can be programmable)
Sampling Rate 10kHz
Time resolution 36us
Time measurement range 0~105s
Time accuracy <±1ms @ 0.001~ 1s
<±0.1% @ >1s
Debounce time 0~25ms (Software controlled)
Binary Output
Quantity 4 pairs, Fast speed
Type Banana type 4.0mm
AC break capacity Vmax:250V(AC)/ Imax:0.5A
DC break capacity Vmax:250V(DC)/ Imax:0.5A
Electrical isolation All pairs isolated
Synchronize port
Satellite synchronization 1 × SMA,Use for GPS antenna interface
Support GPS and Beidou Satellite
Fiber IRIG-B 2 × ST,1 for transmission, 1 for receiving
Electric IRIG-B 1 × 6Pin 5.08mm phoenix terminal
1 for transmission, 1 for receiving
External trigger synchronization 1 × 4Pin 5.08mm phoenix terminal
external trigger input + external trigger output
Communication interface
Ethernet 2 × RJ45 ,10/100M
WIFI Inbuilt WIFI DHCP service
Serial port 1 × RS232
USB 2 × USB2
Weight & Size
Size 390mm×256mm×140mm
Weight 10kg
Display 9.7inch LCD, touch screen
Keypad Number key + direction key
Power supply
Nominal voltage 220V/110V (AC)
Allowable voltage 85 - 265 VAC ;127V~350V(DC)
Nominal Frequency 50Hz
Allowable Frequency 47-63Hz
Current 10A max
Power Consumption 1200VA max
Connection Type Standard AC socket 60320
Working environment
Operating temperature -10~+55 ℃
Relative humidity 5~95%,Non-condensation
Storage temperature -20℃ ~ +70℃
Atmospheric pressure 80kPa~110 kPa(altitude 2000m or lower)

 

 

Advance:

 

(Optional modules)

IEC61850 functions:

Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8)
Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function.
Up to 36 sampling value channels can be mapped.

 

Fiber port (LC type) (Hardware Can be Pre-installed)
Type 100Base-FX (100Mbit,Fiber, full duplex)
Port Number 8 Pairs
Cable model 62.5/125μm(Multiple-mode fiber, orange)
Wave length 1310nm
Transmission distance > 1Km
Status indication SPD Green (lights): active connection
LinkAcT Yellow (blinking): data exchange
Fiber serial port (ST type)
Standard IEC60044-7/8
Port Number 6 for transmission, 2 for receive
Wave length 850nm


10 Low-Level channels signal output function:

Low-level signal output (Hardware Can be Pre-installed)
Output channels 10 channels
Output port type Phoenix terminal
Output range 8x0~8Vrms; 2x0~20mA
Max current output Rating 2mA, 10mA transient max.
Accuracy

(0.01~0.8 Vrms/0~2mA):<0.05% Typ. / <0.1% Guar.

(0.8~8 Vrms/2~20mA): <0.02% Typ. / <0.05% Guar.

Distortion (THD+N) < 0.05% Typ. / <0.1% Guar.
Resolution 250µV
Harmonic(THD%) (THD%)<0.1%
Frequency range DC~1.0kHz
Frequency accuracy 0.002%(Normal frequency)
Frequency resolution 0.001Hz
Phase range 0~359.9°
Phase accuracy <0.1°,50/60Hz
Phase resolution ±0.1°

 

 

Transducer Calibration Function:

 

 

DC Measurement Input (Hardware Can be Pre-installed)
Voltage Input Range 0~±10V dc
Max Input ±11V dc
Accuracy Accuracy <0.05% rg Typ. <0.02% rg Guar.
Input Impedance 1M ohm
Current Input Range 0~±1mA / 1~±20mA, auto range
Max Input 600mA
Accuracy Accuracy <0.05% rg Typ. <0.02% rg Guar.
Input Impedance 15 ohm
 

 

Energy Meter Calibration Function:

 

Energy Meter Calibration (Hardware Can be Pre-installed)
Sensor Usage Mechanical meters / Electronic meters
Sensor Output High lever:>4.5V, Low level:<0.2V
Pulse Input 1 pulse input port, 5Vdc high level valid only.
Pulse Range 500KHz pulse input Max.
Pulse Output 1 Transistor output, Open-collector, 5Vdc/5mA
 

 

 

Contact Details
Kingsine Electric Automation Co., Ltd.

Contact Person: Yana

Tel: 13418725012

Send your inquiry directly to us (0 / 3000)