Product Details:
Payment & Shipping Terms:
|
Time Resolution: | 10us | Operating Temperature: | -10℃~55℃ |
---|---|---|---|
Weight: | 17.5 Kg | Dimensions(W X D X H): | 468×375×164(mm) |
Nominal Input Voltage: | 100~240Vac | Nominal Frequency: | 50/60Hz |
High Light: | K3163i Protection Relay Testing,IEC 61850 Three Phase Relay Tester,IEC61850 K3163i |
Three Phase IEC61850 K3163i Protection Relay Testing
Description Of IEC61850 Relay Test Set
Relay protection microcomputer test device plays a key role in operating electricity power systems reliably and safely. It is the testing device used in professional field of microcomputer protection, relay protection, excitation measurement, fault recorder.
Feature Of Intelligent Relay Tester
● | Universal Relay Test Applications |
● | 10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics. |
● | 13 Low-level channels outputs up to 8Vac/10Vdc max. |
● | 100/1000Mbit Fiber port for SMV and GOOSE simulations |
● | Variable battery simulator, DC 0-350V, 140Watts max. |
● | Transient play back up to 3KHz |
● | Fully function KRT software testing modules |
● | Graphical test modules and templates for testing of various relays |
● | Quick relay testing facility in Manual mode |
● | Shot/Search/Check, Point & Click testing |
Specification Of Overcurrent Relay Test Set
Voltage Outputs | ||
Output Range & Power | 4×310 V ac (L-N) | 124 VA max each |
3×350 V dc (L-N) | 140 W max each | |
Accuracy | ±2mV @ <2V ac <0.015%Rd+0.005Rg Typ. @ 2~310V ac <0.04%Rd+0.01Rg Guar. @ 2~310V ac |
|
±10mV @ <5V dc ±0.5% @ ≥5V dc |
||
Voltage Range | Range I : 30V | |
Range II : 310V | ||
Automatic Range | ||
DC Offset | <20mV Typ./ <100mV Guar | |
Resolution | 1mV | |
Distortion | <0.015%Typ. / <0.05% Guar. | |
Current Outputs | ||
Output Range & Power | 6×35A ac (L-N) | 480 VA max each |
3×70A ac (2L-N) | 850 VA max each | |
1×100A ac (6L-N) | 1200 VA max | |
3×20A dc (L-N) | 300W max each | |
Accuracy | ±1mA @ <0.5A ac <0.02%Rd+0.01Rg Typ. @ 0.5A~35A ac <0.05%Rd+0.02Rg Guar. @ 0.5A~35A ac |
|
±5mA @ <1A dc ±0.5% @ ≥1A dc |
||
Current Range | Range I: 3A | |
Range II: 35A | ||
Automatic Range | ||
DC Offset | <3mA Typ./ <10mA Guar | |
Resolution | 1mA | |
Distortion | <0.025%Typ. / <0.07% Guar. | |
Low-Level Output | ||
Quantity | 13 Channels, 16 pin combination female socket | |
Voltage Outputs Range | AC 0~8V, DC 0~10V | |
Current Outputs Range | Nominal 2mA, 10mA max transient | |
Output Power | ≥0.5VA | |
Accuracy | (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar. (0.8~8 Vrms): <0.02% Typ. / <0.05% Guar. |
|
Resolution | 0.25mV | |
Distortion (THD%) | <0.05% Typ. / <0.1% Guar. | |
Frequency Range | 0~3000KHz | |
DC Offset | <0.15mV Typ. / <1.5mV Guar. |
Advantage Of Frequency Relay Test System
● | Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8) |
● | Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function. |
● | Up to 36 sampling value channels can be mapped. |
FAQ
Q: Can the relay protection tester show the impedance curve?
A: Yes.
Q: What is your technical advantages?
A: Our products with All-in-One design, weight < 17.5kg.High Power & Accuracy with 6x35A & 4x310V analog outputs and Complying IEC61850 Sampling Value & GOOSE.
Q: How long is the warranty period?
A: 3-Years guarantee of free repair and life-long maintenance
Contact Person: Amy
Tel: +8613603051120