Product Details:
Payment & Shipping Terms:
|
High Light: | Universal Protection Relay Testing Complying IEC61850,GOOSE Protection Relay Testing |
---|
◆ Digital signal complying IEC61850-9-1 / IEC61850-9-2 protocols.
◆ Synchronize with GPS,IRIG-B.
◆ Suitable testing for all kinds of electromagnetic relays,microcomputer relays.
Model | Current Outputs | Voltage Outputs | ||||
K3166i | 6×35A@450VA max / 3×70A@850VA max | 7×310V@90VA max | ||||
K3163i | 6×35A@450VA max / 3×70A@850VA max | 4×310V@124VA max | ||||
K3130i | 3×35A@450VA max | 4×310V@124VA max |
1. Two 100Mbit Optical Fiber ports for SMV and GOOSE simulations(exchangeable with RJ45).
2. 6×35A & 4×310V independent high burden output channels.
3. 13 channels independent low-level signal outputs.
4. AC/DC measurement(8 channels inputs,class 0.05,0-600V/0-5A,auto range).
5. Transducer calibartion (class 0.02).
6. Energy meter calibration(Mechanical & Electronic meters).
7. Transient play back up to 3KHZ.
8. Light weight <18kg.
9.Fully function KRT software testing modules.
10.3-Years guarantee of free repair and life-long maintenance.
11.Free software upgrade.
Testing Items | ANSI® No. | |||||
IEC61850 numerical IEDs relay & merge unit | -- | |||||
Distance protection relay | 21 | |||||
Synchronising or synchronism-check relays | 25 | |||||
Undervoltage relays | 27 | |||||
Directional Power relays | 32 | |||||
Undercurrent or underpower relays | 37 | |||||
Negative sequence overcurrent relays | 46 | |||||
Overcurrent/ground fault relays | 50 | |||||
Inverse time overcurrent/ground fault relays | 51 | |||||
Power factor relays | 55 | |||||
Overvoltage relays | 59 | |||||
Voltage or current balance relays | 60 | |||||
Directional overcurrent relays | 67 | |||||
Directional ground fault relays | 67N | |||||
DC overcurrent relays | 76 | |||||
Phase-angle measuring or out-of-step protection relays | 78 | |||||
Automatic reclosing devices | 79 | |||||
Frequency relays | 81 | |||||
Motor overload protection relays | 86 | |||||
Differential protection relays | 87 | |||||
Directional voltage relays | 91 | |||||
Voltage and power directional relays | 92 | |||||
Tripping relays | 94 | |||||
Voltage regulating relays | -- | |||||
Overimpedance relays, Z> | -- | |||||
Underimpedance relays, Z | -- | |||||
Time-delay relays | -- |
1. 10 Channels (6×35A & 4×310V) outputs, each output channels are independent and simultaneous
control of magnitude, phase angle and frequency values, able to inject DC, AC sine wave and up
to 20 × harmonics.
2. Variable battery simulator, DC 0-350V, 140Watts max.
3. 13 Low-level channels outputs up to 8Vac/10Vdc max.
4. 0-600V / 0-5A AC/DC measurement in 0.05 class.
5. Graphical test modules and templates for testing of various relays.
6. Quick relay testing facility in Manual mode.
7. Shot/Search/Check, Point & Click testing.
8. RIO/XRIO import & export facility.
9. Switch on to fault test(SOTF).
10.Power system model for dynamic testing.
11.Inbuilt GPS and IRIG-B sync end-to-end testing.
12.Online Vector display.
13.Automatic test results assume.
14.Automatic test report creation.
15.Anti-clipping detect,wrong wiring connect alarm and self-protect, overload and overheat protection.
Voltage Outputs |
||||||
Output Range & Power | 4×310V ac (L-N) | 124VA max each | ||||
2×620V ac (L-L) | 248VA max each | |||||
3×350V dc (L-N) | 140W max each | |||||
Accuracy | AC:<0.03%Rd + 0.02Rg Typ. / <0.07%Rd + 0.03Rg Guar. | |||||
DC: ±10mV @<5V,±0.5% @ ≥5V | ||||||
Resolution | 1mV | |||||
Distortion | <0.05% Typ. / <0.1% Guar. | |||||
Current Outputs | ||||||
Output Range & Power | 6×35A ac(L-N) | 450VA max single | ||||
3×70A ac(2L-N) | 850VA max single | |||||
1×100A ac(6L-N) | 1200VA max | |||||
3×20A dc(L-N) | 300W max each | |||||
Accuracy | AC:<0.03%Rd + 0.02Rg Typ. / <0.15%Rd + 0.05Rg Guar. | |||||
DC: ±5mA @<1A,±0.5% @ ≥1A | ||||||
Resolution | 1mA | |||||
Distortion | <0.05%Typ. / <0.1% Guar. | |||||
Low-Level Output |
||||||
Quantity | 13 Channels, 16 pin aviation socket | |||||
Voltage outputs range | AC 0-8V, DC 0-10V | |||||
Current outputs range | Nominal 2mA, 10mA max transient | |||||
Output Power | ≥0.5VA | |||||
Accuracy | (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar. | |||||
(0.8~8 Vrms):<0.02% Typ. / <0.05% Guar. | ||||||
Resolution | 0.25mV | |||||
Distortion(THD%) | <0.05%Typ. / <0.1% Guar. | |||||
Frequency & Phase Angle |
||||||
Frequency Range | DC~1KHZ, 3KHZ transient | |||||
Frequency Accuracy | ±0.5ppm | |||||
Frequency Resolution | 0.001Hz | |||||
Phase Range | 0°~360° | |||||
Phase Accuracy | <0.05°Typ. / <0.1° Guar. 50/60Hz | |||||
Phase Resolution | 0.001° | |||||
IEC61850 Fiber & GOOSE Ethernet Ports (Optional Function) |
||||||
Fiber Ports |
2×100 Base-FX Full Duplex, LC type
(Optional to 10/100Mbit, Ethernet RJ45 type) |
|||||
Fiber Type | 62.5/125um (Multiple optical fiber, Orange Red) | |||||
Wavelength | 1310nm | |||||
Transmit Distance | >1Km | |||||
Indicator |
Spd Green (light): Valid connection
|
|||||
Note: Hardware is ready, to be actived. | ||||||
Aux. DC Voltage Source(Battery simulator) |
||||||
Range | 0~350V @ 180W max | |||||
Accuracy | 0.5%Rg Guar. | |||||
Binary Input |
||||||
Quantity | 8 pairs | |||||
Type | wet/dry, measurement | |||||
Threshold | 10~600Vdc or potential free, Programmable | |||||
Time resolution | 100us | |||||
Debounce time | 0~25ms (Software Controlled) | |||||
Time range | Infinite | |||||
Time errors | ±1ms @ 0.001~1s, ±0.1% @>1s | |||||
Galvanic isolation | 4 isolated with each 2 pairs | |||||
Binary Output (Relay Type) |
||||||
Quantity | 4pairs | |||||
Type | Potential free relay contacts,software controlled | |||||
Break Capacity AC | Vmax: 400Vac / Imax:8A / Pmax:2500VA | |||||
Break Capacity DC | Vmax: 300Vdc / Imax:5A / Pmax:150W | |||||
Binary Output (Semiconductor Type) |
||||||
Quantity | 4pairs | |||||
Type | Open-collector, 14 pin Aviation socket | |||||
Break Capacity DC |
5~15Vdc / 5mA, 10mA max
|
|||||
Response time | 100us | |||||
Synchronization |
||||||
Synchronization Mode | GPS, SMA type antenna connector / IRIG-B / IEEE1588 | |||||
Power supply & Environment |
||||||
Nominal Input Voltage | 100~240Vac | |||||
Permissible Input Voltage | 85~264Vac, 125~350VDC | |||||
Nominal Frequency | 50/60Hz | |||||
Permissible Frequency | 45Hz~65Hz | |||||
Power Consumption | 1500 VA max | |||||
Connection Type | Standard AC socket 60320 | |||||
Operating Temperature | -10℃~55℃ | |||||
Storage Temperature | -20℃~70℃ | |||||
Humidity | <95%RH, non-condensing | |||||
Others |
||||||
PC Connection | RJ45 Ethernet, 10/100M | |||||
Grounding Terminal | 4mm banana socket | |||||
Weight | 18Kg | |||||
Dimensions(W×D×H) | 468×375×164(mm) |
DC Measurement Input(Transducer calibrator) * Hardware is ready,to be actived. |
||||||
Voltage input | Range | 0~±10V dc | ||||
Max Input | ±11V dc | |||||
Accuracy | <0.02% rg Typ. / <0.05% rg Guar. | |||||
Input Impedance | 1M ohm | |||||
Current Input | Range | 0~±1mA / 1~20mA, auto range | ||||
Max Input | 600mA | |||||
Accuracy | <0.02% rg Typ. / <0.05% rg Guar. | |||||
Input Impedance | 15 ohm | |||||
AC / DC Measurement Input( Standard meter ) * Require extra PCB installed in factory only |
||||||
Input Quantity | 8 channels (blend with binary input pairs) | |||||
Voltage rang | 0~600Vrms (Rg: 0.1V,1V,10V,60V,600V) | |||||
Voltage accuracy | <0.05% Rg | |||||
Current range | Shunt input: 0~5Arms / 0~30Arms (Optional) | |||||
Current accuracy | <0.1% Rg | |||||
Sample rate | 10KHz | |||||
Input impedance | 600KΩ | |||||
Frequency range | 45~65Hz, Accuracy<0.01Hz | |||||
Phase accuracy | 0~360°,<0.2° Typ. | |||||
|
||||||
Energy Meter Calibration * Hardware is ready,to be actived |
||||||
Sensor Usage | Mechanical meters / Electronic meters | |||||
Sensor Output | High level : >4.5V, Low level: <0.2V | |||||
Pulse Input | 1 pulse input port | |||||
Pulse Range | 500KHz pulse input Max. | |||||
Pulse Output | 1 Transistor output, Open-collector, 5-15Vdc/5mA |
Contact Person: Amy
Tel: +8613603051120